ADJUSTABLE PRESSURE REDUCING& STABILIZING VALVE ENYX741X
A. ADJUSTABLE PRESSURE REDUCING& STABILIZING VALVE PURPOSE
ENYX741X Adjustable Pressure Reducing & Stabilizing Valve is mounted on the pipeline of high buildings and other supply systems to lower the higher upper-stream pressure to the one used for the down-stream in line with the requirements.

B. ADJUSTABLE PRESSURE REDUCING& STABILIZING VALVE FEATURE
  1. Reliable pressure reducing effect. Either the inlet pressure or the flow variation will not influence the outlet pressure; both dynamic and static pressures can be reduced.
  2. Easy debugging and operation. Just adjusting the adjustable screw of the pilot valve can get an accurate and stable outlet pressure.
  3. Good effect of energy saving. The valve body is so designed as full-path streamline straight-flow type, resulting in the small pressure loss, big flow, small volume and light weight.

C. ADJUSTABLE PRESSURE REDUCING& STABILIZING VALVE BRIEF FIGURE OF STRUCTURE
1. Small Ball Valve 2. Pilot Valve 3. Strainer 4. Small Ball Valve
Diaphragm type
1.Small Float Ball Valve 2. Pilot Valve 3. Needle Valve 4. Strainer 5. Small Ball Valve
Piston type

D. ADJUSTABLE PRESSURE REDUCING& STABILIZING VALVE MAIN EXTERNAL AND CONNECTION DIMENSIONS
DN L D D1 n-d H
1.0Mpa 1.6 Mpa 2.5 Mpa 1.0Mpa 1.6 Mpa 2.5 Mpa 1.0Mpa 1.6 Mpa 2.5 Mpa
50 205 165 165 165 125 125 125 4-18 4-18 4-18 300
65 216 185 185 185 145 145 145 4-18 4-18 8-18 337
80 250 200 200 200 160 160 160 8-18 8-18 8-18 467
100 320 220 220 235 180 180 190 8-18 8-18 8-22 520
125 365 250 250 270 210 210 220 8-18 8-18 8-22 580
150 415 285 285 300 240 240 250 8-22 8-22 8-26 640
200 500 340 340 360 295 295 310 8-22 12-22 12-26 778
250 605 395 405 425 350 355 370 12-22 12-26 12-26 889
300 698 445 460 485 400 410 430 12-22 12-26 12-30 1010
350 787 505 520 555 460 470 490 16-22 16-26 16-30 1037
400 914 565 580 620 515 525 550 16-26 16-30 16-33 1264
450 978 615 640 670 565 585 600 20-26 20-30 16-36 1294
500 978 670 715 730 620 650 660 20-26 20-33 20-36 1324
600 1150 780 840 845 725 770 770 20-30 20-36 20-39 1600
700 1300 895 910 960 840 840 875 24—30 24-36 24-42 1750
800 1450 1015 1025 1085 950 950 990 24—33 24-39 24-48 1900

E. ADJUSTABLE PRESSURE REDUCING& STABILIZING VALVE SCHEMATIC DIAGRAM OF INSTALLATION
H142X HYDRAULIC WATER LEVEL CONTROL VALVE
Note: Either elastic seat ring sealed gate valve or butterfly valve can be selected from the schematic of installation. Recommend to select the butterfly valve in case of =DN350.

The technical data subject to amend without notice